One-Way Wide Module (Skip) Joist Concrete Floor System Design
A typical floor plan of a 5-story office building is shown below. Wide-module joists, or “skip” joists, are similar to standard one-way joists, except the pans are 53 in. or 66 in. wide. For the 53 in. pans, the pan depth varies from 16 in. to 24 in., and for 66 in. pans, the range is 14 in. to 24 in. Wide-module systems are economical for long spans with heavy loads and improved vibration resistance (see references). The gravity loads treatment is shown in this example and the lateral load effects are resisted by reinforced concrete shear walls. The design procedures shown in ACI 318-14 are illustrated in detail in this example. The hand solution is also used for a detailed comparison with the analysis and design results of the engineering software program spBeam.
Figure 1 – One-Way Wide Module Joist Concrete Floor Framing System
Contents
1.1. Preliminary slab thickness and joist dimensions
2. Design of Structural Members
2.1.1. Determination of span loads
2.1.2. Determination of design moment and shear
2.1.6. Computer Program Solution
2.1.7. Summary and Comparison of Results
2.1.8. Conclusions and Observations
2.2.1. Determination of span loads
2.2.2. Determination of design moment and shear
2.2.6. Computer Program Solution
2.2.7. Summary and Comparison of Results
2.2.8. Conclusions and Observations
2.3. Design of Beam along Grid B (Interior Frame)
2.3.1. Determination of span loads
2.3.2. Determination of design moment and shear
2.3.6. Computer Program Solution
2.3.7. Summary and Comparison of Results
2.3.8. Conclusions and Observations
2.4. Design of Beam along Grid A (Exterior Frame)
2.4.1. Determination of span loads
2.4.2. Determination of design flexural moment, shear, and torsional moment
2.4.3. Flexural, Shear, and Torsion Design
2.4.5. Computer Program Solution
2.4.6. Summary and Comparison of Results
2.4.7. Conclusions and Observations
2.5. Design of Interior, Edge, and Corner Columns
2.5.1. Determination of factored loads
2.5.2. Column Capacity Diagram (Axial-Moment Interaction)
Code
Building Code Requirements for Structural Concrete (ACI 318-14) and Commentary (ACI 318R-14)
Minimum Design Loads for Buildings and Other Structures (ASCE/SEI 7-10)
International Code Council, 2012 International Building Code, Washington, D.C., 2012
References
Notes on ACI 318-11 Building Code Requirements for Structural Concrete, Twelfth Edition, 2013 Portland Cement Association.
Concrete Floor Systems (Guide to Estimating and Economizing), Second Edition, 2002 David A. Fanella
Simplified Design of Reinforced Concrete Buildings, Fourth Edition, 2011 Mahmoud E. Kamara and Lawrence C. Novak
Design Data
Floor-to-Floor Height = 12 ft (provided by architectural drawings)
wc = 150 pcf
fc’ = 5,000 psi
fy = 60,000 psi (For flexural reinforcement)
fyt = 60,000 psi (For shear and torsional reinforcement)
Superimposed dead load, SDL = 20 psf framed partitions, wood studs plaster 2 sides
ASCE/SEI 7-10 (Table C3-1)
Typical Floor Level, Live load, Lo = 80 psf (Office building) ASCE/SEI 7-10 (Table 4-1)
Roof Live Load, Lo = 20 psf (Ordinary flat roofs) ASCE/SEI 7-10 (Table 4-1)
Required fire resistance rating = 2 hours
Solution
In this example deflection will be calculated and checked to satisfy project deflection limits. Minimum member thickness and depths from ACI 318-14 will be used for preliminary sizing.
a. One-way Slab
Using minimum thickness for solid one-way slabs in Table 7.3.1.1 for the solid slab spanning between the ribs.
End Spans: in ACI 318-14 (Table 7.3.1.1)
Interior Spans: in ACI 318-14 (Table 7.3.1.1)
The minimum slab thickness for wide-module joists for 2-hour fire rating is 4.6 in.
IBC 2012 (Table 720.1(3))
Therefore, select a slab thickness of 5 in. for all spans.
b. One-way Joist
The wide-module joist systems do not meet the limitations of ACI 318-14, 9.8.1.1 through 9.8.1.4. Therefore, the structural members of this type of joist construction shall be designed with standard provisions for slabs and beams.
ACI 318-14 (9.8.1.8)
Using minimum thickness for non-prestressed beams in Table 9.3.1.1. For the ribs (part of the joists) supporting the solid slab.
End Span: in (governs) ACI 318-14 (Table 9.3.1.1)
Interior Span: in ACI 318-14 (Table 9.3.1.1)
Therefore, select rib depth of 16 in. for a total joist depth of 21 in.
Figure 2 – Slab and Joist Dimensions
a. Interior Columns
Select a preliminary size based on the axial load demand. Determine interior column loads as follows:
The governing load combination: ACI 318-14 (Eq. 5.3.1b)
Where:
D = Dead Load; L= Live Load; Lr= Roof Live Load
Typical Floor Level Loads
# of Floors = 4
Dead Loads, D
Self-weight of wide-module joist system (see Figure 2):
Joist average thickness =
Weight of the joist = 0.5524 x 150 pcf = 82.83 psf.
Superimposed dead load = 20 psf
Live Load, L: Calculate the live load reduction per ASCE/SEI 7-10
ASCE/SEI 7-10 (Eq. 4-1)
Where:
L = reduced design live load per ft2 of area supported by the member
Lo = unreduced design live load per ft2 of area supported by the member = 80 psf
KLL = live load element factor ASCE/SEI 7-10 (Table 4-2)
AT = tributary area ft2
psf
Which satisfies requirement for members supporting two or more floors.
ASCE/SEI 7-10 (4.7.2)
Roof Level Loads
Dead Loads, D
Self-weight of wide-module joist system (see Figure 2):
Joist average thickness =
Weight of the joist = 0.5524 x 150 pcf = 82.83 psf.
No superimposed dead load at the roof
Roof Live Load, Lr: Calculate the roof live load reduction
; ASCE/SEI 7-10 (Eq 4-2)
Where:
psf
since ft2 ft2
for flat roof
psf
Total Factored Load on 1st story interior column (@ 1st interior support)
Total Floor Load kips
Total Roof Load lbkips
Assume 24 in square column with 4 – # 11 vertical bars with design axial strength, of
ACI 318-14 (22.4.2)
lb
kips
Column Self-weight kips
Total Reaction @ 1st interior support kips kips.
Therefore, the preliminary interior column size of 24 in. x 24 in. is adequate.
b. Edge (Exterior) Columns
Select a preliminary size based on the axial load demand. Therefore, the load take-down for an edge column is done as follows:
The governing load combination: ACI 318-14 (Eq. 5.3.1b)
Typical Floor Level Loads
# of Floors = 4
Dead Loads, D
Self-weight of wide-module joist system (see Figure 2):
Weight of the joist = 82.83 psf.
Superimposed dead load = 20 psf
Live Load, L: Calculate the live load reduction per ASCE/SEI 7-10
ASCE/SEI 7-10 (Eq. 4-1)
Where:
L = reduced design live load per ft2 of area supported by the member
Lo = unreduced design live load per ft2 of area supported by the member = 80 psf
KLL = live load element factor = 4 ASCE/SEI 7-10 (Table 4-2)
AT = tributary area ft2
psf
Which satisfies requirement for members supporting two or more floors.
ASCE/SEI 7-10 (4.7.2)
Roof Level Loads
Dead Loads, D
Weight of the joist = 82.83 psf.
No superimposed dead load at the roof
Roof Live Load, Lr: Calculate the roof live load reduction
; ASCE/SEI 7-10 (Eq 4-2)
Where:
psf
, since 200 ft2 < At = 480 ft2 < 600 ft2
for flat roof
psf
Total Factored Load on 1st story edge column (@ 1st interior support)
Total Floor Load kips
Total Roof Load lbkips
Assume 20 in square column with 4 – # 11 vertical bars with design axial strength, of
ACI 318-14 (22.4.2)
lb
kips
Column Self-weight kips
Total Reaction @ 1st interior support kips kips.
Therefore, the preliminary edge column size of 20 in. x 20 in. is adequate.
c. Corner Columns
Select a preliminary size based on the axial load demand. Therefore, the load take-down for a corner column is done as follows:
The governing load combination: ACI 318-14 (Eq. 5.3.1b)
Typical Floor Level Loads
# of Floors = 4
Dead Loads, D
Self-weight of wide-module joist system (see Figure 2):
Weight of the joist = 82.83 psf.
Superimposed dead load = 20 psf
Live Load, L: Calculate the live load reduction per ASCE/SEI 7-10
ASCE/SEI 7-10 (Eq. 4-1)
Where:
L = reduced design live load per ft2 of area supported by the member
Lo = unreduced design live load per ft2 of area supported by the member = 80 psf
KLL = live load element factor = 4 ASCE/SEI 7-10 (Table 4-2)
AT = tributary area ft2
psf
Which satisfies requirement for members supporting two or more floors.
ASCE/SEI 7-10 (4.7.2)
Roof Level Loads
Dead Loads, D
Weight of the joist = 82.83 psf.
No superimposed dead load at the roof
Roof Live Load, Lr: Calculate the roof live load reduction
; ASCE/SEI 7-10 (Eq 4-2)
Where:
psf
, since 200 ft2 < At = 240 ft2 < 600 ft2
for flat roof
psf
Total Factored Load on 1st story corner column (@ exterior support)
Total Floor Load kips
Total Roof Load lbkips
Assume 20 in square column with 4 – # 11 vertical bars with design axial strength, of
ACI 318-14 (22.4.2)
lb
kips
Column Self-weight kips
Total Reaction @ exterior support kips kips.
Therefore, the preliminary edge column size of 20 in. x 20 in. is adequate.
The design of the following structural members is performed and compared with results of the engineering software program spBeam:
2.1. One-Way Slab
2.2. One-Way Joist
2.3. Interior Beam
2.4. Exterior Beam
2.5. Interior Column
A unit strip of 1 ft is considered for the design of slab spanning between ribs. Note that ACI 318-14 does not allow live load reduction for one-way slabs.
Figure 2.1 – Partial plan view illustrating slab design strip
Slab design involves the following steps:
2.1.1. Determination of span loads
2.1.2. Determination of design moments and shears
2.1.3. Flexural Design
2.1.4. Shear Design
2.1.5. Deflections
2.1.6. Computer Program Solution
2.1.7. Summary and comparison of design results
2.1.8. Conclusions and observations
The following gravity load combinations are considered:
ACI 318-14 (Eq. 5.3.1a)
kips/ft per ft
ACI 318-14 (Eq. 5.3.1b)
kips/ft per ft
Span loads are governed by the second load combination.
The factored moment and shear can be determined using the simplified method if the requirements are satisfied: ACI 318-14 (6.5.1)
ü Members are prismatic.
ü Loads are uniformly distributed.
ü L ≤ 3D (0.08 kips/ft per ft ≤ 3 x 0.0825 kips/ft per ft)
ü There are at least two spans.
ü The longer of two adjacent spans does not exceed the shorter by more than 20 percent.
Thus, the approximate coefficients can be used. The factored moments and shears are determined and summarized in the following tables. ACI 318-14 (Table 6.5.2 and Table 6.5.3)
Table 2.1.2.1 – One-Way Slab Design Moment Values |
||
Location |
Design Moment Value |
|
End Spans |
Exterior Support Negative |
ft-kips/ft |
Mid-span |
ft-kips/ft |
|
Interior Support Negative |
ft-kips/ft |
|
Interior Spans |
Mid-span Positive |
ft-kips/ft |
Support Negative |
ft-kips/ft |
Table 2.1.2.2 – One-Way Slab Design Shear Values |
|
Location |
Design Shear Value |
End Span at Face of First Interior Support |
kips/ft |
At Face of all other Supports |
kips/ft |
For the one-way slab of a wide-module joist system, a single layer of longitudinal reinforcement is provided. The first interior support negative moment governs the design as tabulated in Table 2.1.2.1. Therefore, it is favorable to place the single layer reinforcement closer to the top fiber of the concrete slab. The required reinforcement shall be calculated for the first interior support negative moment first. The required reinforcement for the end span positive moment shall also be calculated as the low effective depth due to the reinforcement location may govern the required reinforcement amount. Finally, the required reinforcement for design shall be checked against the minimum shrinkage and temperature reinforcement requirement per ACI 318-14 (24.4.3.2).
Calculate the required reinforcement to resist the first interior support negative moment:
ft-kips/ft
Use welded wire fabric reinforcement, 6 x 6-W5.5 x W5.5 with 1.5 in. concrete cover. The distance from extreme compression fiber to the centroid of longitudinal tension reinforcement, d, is calculated below:
in.
To determine the area of steel, assumptions have to be made whether the section is tension or compression controlled, and regarding the distance between the resultant compression and tension forces along the slab section (jd). In this example, tension-controlled section will be assumed so the reduction factoris equal to 0.9, and jd will be taken equal to 0.95d. The assumptions will be verified once the area of steel is finalized.
Assumein.
Unit strip width, b = 12 in.
in.2/ft
Recalculate ‘a’ for the actual As = 1.31 in.2: in.
in.
Therefore, the assumption that section is tension-controlled is valid.
in.2/ft
Calculate the required reinforcement to resist the positive moment:
ft-kips/ft
The distance from extreme compression fiber to the centroid of longitudinal tension reinforcement:
in.
To determine the area of steel, assumptions have to be made whether the section is tension or compression controlled, and regarding the distance between the resultant compression and tension forces along the slab section (jd). In this example, tension-controlled section will be assumed so the reduction factoris equal to 0.9, and jd will be taken equal to 0.95d. The assumptions will be verified once the area of steel is finalized.
Assumein.
Unit strip width, b = 12 in.
in.2/ft
Recalculate ‘a’ for the actual As = 0.070 in.2: in.
in.
Therefore, the assumption that section is tension-controlled is valid.
in.2/ft
Check the shrinkage and temperature reinforcement requirement:
in.2 / ft ACI 318-14 (Table 24.4.3.2)
Check reinforcement spacing for crack control:
The maximum spacing of the flexural reinforcement closest to the tension face of the slab shall be:
, but not greater than ACI 318-14 (Table 24.3.2)
Where:
Maximum reinforcement spacing for crack control, in
Calculated stress in reinforcement closest to the tension face at service load, ksi
The least distance from surface of reinforcement to the tension face, in
psi ACI 318-14 (24.3.2.1)
in. for reinforcement resisting negative moment at supports (i.e. tension at the top)
in. for reinforcement resisting positive moment at mid-span (i.e. tension at the bottom)
Thus,
At supports
in (governs @ support)
But not greater than in.
At mid-span
in (governs @ mid-span)
But not greater than in.
Therefore, for this one-way slab, the shrinkage and temperature reinforcement requirement per ACI 318-14 (Table 24.4.3.2) governs the required reinforcement area (in2/ft) and crack control requirement per ACI 318-14 (Table 24.3.2) governs the reinforcement spacing (in.).
The most feasible reinforcement solution that meets both requirements mentioned above is to provide welded wire fabric reinforcement, 6 x 6-W5.5 x W5.5. Note that the welded wire reinforcement selected provides minimum shrinkage and temperature reinforcement in the slab direction parallel to the joists as well. Alternately, deformed bars can be utilized in lieu of welded wire fabric. It should be noted that two conditions specific to this design contribute to having such a stringent spacing requirement.
These are listed below:
- The 5 in. slab has a single layer reinforcement that is placed near the top surface (i.e. clear cover from the top surface to the reinforcement is 1.5 in. This result in a high cc value for the calculation of reinforcement spacing for crack control due to positive moment.
- The stress in reinforcement closest to the tension face at service load, fs, is taken as 2/3 fy as permitted by ACI 318-14 without calculation. It is very likely that under the loading considered, the stress in the steel will be lower than 2/3 fy. The fs value is expected to be in the range of 1/3 fy to 1/2 fy. Even if it is assumed to be 1/2 fy , s value will be 12 in.
From Table 2.1.2.2 above, the shear value in end span at face of first interior support governs.
kips/ft
The design shear at a distance, d, away from the face of support,
kips/ft
Shear strength provided by concrete
ACI 318-14 (Eq. 22.5.5.1)
lb/ft kips/ft
kips/ft kips/ft .
Therefore, the slab shear capacity is adequate.
Since the preliminary slab thickness met minimum thickness requirement, the deflection calculations are not required. Unless governed by fire rating requirements; as in this example; lesser thicknesses and consequently cost savings can be achieved through deflection computations. Deflection values are calculated and provided for every model created by spBeam Program and can be used by the engineer to make additional optimization decisions.
spBeam Program can be utilized to analysis and design beams and one-way slab systems. The one-way slab is modeled as 1-ft unit strip supported on ribs. The ribs provide some rotational stiffness at the supports. In spBeam solution, the rotational stiffness is assumed as 32,000* kip-in/rad for modeling the joist supports. Also, for one-way slab run, the rib widths assumed as 6 in. and modeled through dummy columns of 6 in. x 12 in. with zero height (i.e. column stiffness is zero, but the 6 in. dimension of the column is utilized to push the design moments 3 in. from the support centerline). In this example, user-defined bar size #2 is defined in spBeam to represent welded wire fabric, W5.5, with the cross-sectional area of 0.055 in2 (see Fig. 2.1.6.1).
Figure 2.1.6.1 – spBeam Reinforcement Database – User-defined Bar Set
The program calculates the internal forces (shear force and bending moment), moment and shear capacities, immediate and long-term deflections, and required reinforcements. The graphical and text results are provided below for input and output of the spBeam program. The graphical and text results are provided here for both input and output of the spBeam model.
* Refer to spBeam manual (Chapter 2 – Special Considerations for One and Two-Way Joist Systems)
* Refer to spBeam manual (Chapter 4 – Defining Boundary Conditions, Rotational Stiffness)
Figure 2.1.6.2 – spBeam Model – Isometric View of 15 Span – 1ft Wide Unit Strip of One-Way Slab
Figure 2.1.6.3 – spBeam Model – Loads (Including Live Load Patterning) units in lb/ft2
Figure 2.1.6.4 – spBeam Model – Internal Forces (Shear Force Diagram and Bending Moment Diagram)
Figure 2.1.6.5 – spBeam Model – Moment Capacity Diagram
Figure 2.1.6.6 – spBeam Model – Shear Capacity Diagram
Figure 2.1.6.7 – spBeam Model – Immediate Deflection Diagram
Figure 2.1.6.8 – spBeam Model – Reinforcement Diagram
Table 2.1.7.1 – Comparison of Hand Solution with spBeam Solution |
||||||
Flexural Design |
||||||
Span Location |
Design Moment (ft-kips/ft) |
Reinforcement Required for Flexure (in2/ft) |
Minimum Reinforcement (in2/ft) (Shrinkage & Temperature Reinforcement) |
|||
End Span |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Interior Negative |
0.69 |
0.63 |
0.046 |
0.042 |
0.108 (2-#2) |
0.108 (2-#2) |
Positive |
0.49 |
0.49 |
0.069 |
0.069 |
0.108 (2-#2) |
0.108 (2-#2) |
Shear Design |
||||||
Span Location |
Vu (kips/ft) |
φVn (kips/ft) |
||||
End Span |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
||
Interior Negative |
0.69 |
0.67 |
2.15 |
2.08 |
Minimum reinforcement requirement governed flexural design in this example. spBeam program enables the user to enter the rotational support springs as boundary conditions for joist supports and evaluate various analysis and design options beyond the limitations of the simplified method. The coefficients traditionally used to determine moments do not address various types of support and geometry.
Typically, in wide-module joist construction, one-way slab is reinforced with single layer reinforcement placed near the top in the primary direction. As seen in this example, this may cause crack control criteria to govern the reinforcement spacing and consequently, it may warrant the use of welded wire fabric reinforcement instead of deformed bar.
The maximum calculated total immediate (instantaneous) deflection (DL + LL) = 0.003 in., this value can be compared with maximum permissible calculated deflection limitation per project criteria in accordance to ACI 318-14. ACI 318-14 (Table 24.2.2)
In addition to deflection results, parametric studies can be performed in spBeam to optimize design and detailing results. Note in the reinforcement diagram (Figure 2.1.6.8) 2-#2 for top reinforcement in the span left and right zones as well as span bottom reinforcement. One layer is suitable by inspection (Figure 2.1.6.5) to meet the required area of steel for top and bottom reinforcement.
The wide-module joists in this floor are considered as beams per ACI 318-14 (9.8.1.8). Therefore, the design of the joist shall conform to the requirements of T-beams per ACI 318-14 (9.2.4).
Figure 2.2 – Partial plan view illustrating one-way joist to be design
Joist design involves the following steps:
2.2.1. Determination of span loads
2.2.2. Determination of design moments and shears
2.2.3. Flexural Design
2.2.4. Shear Design
2.2.5. Deflections
2.2.6. Computer Program Solution
2.2.7. Summary and comparison of design results
2.2.8. Conclusions and observations
The following gravity load combinations are considered:
ACI 318-14 (Eq. 5.3.1a)
kips/ft
ACI 318-14 (Eq. 5.3.1b)
kips/ft
Span loads are governed by the second load combination.
Note that for Floor Live Load Reduction per ASCE/SEI 7-10:
ASCE/SEI 7-10 (Eq. 4-1)
Where:
Live Load Element Factor, for interior beams ASCE/SEI 7-10 (Table 4-2)
Tributary Area ft2
Since ft2 ft2, live load reduction is not applicable.
The factored moment and shear can be determined using the simplified method if the requirements are satisfied: ACI 318-14 (6.5.1)
ü Members are prismatic.
ü Loads are uniformly distributed.
ü L ≤ 3D (0.48 kips/ft ≤ 3 x 0.62 kips/ft)
ü There are at least two spans.
ü The longer of two adjacent spans does not exceed the shorter by more than 20 percent.
Thus, the approximate coefficients can be used. The factored moments and shears are determined and summarized in the following tables. ACI 318-14 (Table 6.5.2 and Table 6.5.3)
Table 2.2.2.1 – One-Way Joist Design Moment Values |
||
Location |
Design Moment Value |
|
End Spans |
Exterior Support Negative |
ft-kips |
Mid-span |
ft-kips |
|
Interior Support Negative |
ft-kips |
|
Interior Spans |
Mid-span Positive |
ft-kips |
Support Negative |
ft-kips |
Table 2.2.2.2 – One-Way Joist Design Shear Values |
|
Location |
Design Shear Value |
End Span at Face of First Interior Support |
kips |
At Face of all other Supports |
kips |
* When support beam is wider than the column, the clear span, ln, of the joists is measured from the face of the column. For calculating negative moments, ln, is taken as the average of the adjacent clear spans.
ACI 318-14 (6.5.2)
For the one-way joist of a wide-module joist system, the end span moment values govern the design as tabulated in Table 2.2.2.1.
Calculate the required reinforcement to resist the first interior support negative moment:
ft-kips
Use #5 reinforcement with 1.5 in. concrete cover. The distance from extreme compression fiber to the centroid of longitudinal tension reinforcement, d, is calculated below:
in.
To determine the area of steel, assumptions have to be made whether the section is tension or compression controlled, and regarding the distance between the resultant compression and tension forces along the slab section (jd). In this example, tension-controlled section will be assumed so the reduction factoris equal to 0.9, and jd will be taken equal to 0.9d since we are designing for the negative moment in a T-beam (narrow compression zone). The assumptions will be verified once the area of steel is finalized.
Assumein.
Joist average width, in.
The required reinforcement at initial trial is calculated as follows:
in.2
Recalculate ‘a’ for the actual As = 1.79 in.2: in.
in.
Therefore, the assumption that section is tension-controlled is valid.
in.2
The minimum reinforcement shall not be less than
in.2 ACI 318-14 (9.6.1.2(a))
And not less than
in.2 ACI 318-14 (9.6.1.2(b))
Part of the negative-moment steel shall be distributed over a width equal to the smaller of the effective flange width (72 in) and in. ACI 318-14 (24.3.4)
Where the effective width of the overhanging flange on each side of the beam web is the smallest of the following: ACI 318-14 (6.3.2.1)
in., where h is the slab thickness.
in., where sw is the clear distance to the adjacent web.
in
Therefore, the effective flange width is 72 in
Provide 6-# 5 bars within 38.4 in width.
in2 in2 o.k.
Calculate the required reinforcement to resist the positive moment:
ft-kips
In the positive moment regions, the beam acts as a T-shaped beam. The effective flange width as was calculated earlier is 72 in.
By assuming #3 bars for joist stirrups and the maximum bar size for joist bottom reinforcement as #7 and following the 1.5 in. concrete cover to reinforcement requirement of beam stirrups per ACI 318-14 (20.6.1), the distance from extreme compression fiber to the centroid of longitudinal tension reinforcement, d, is calculated below:
in
Since we are designing for the positive moment in a T-Beam (wide compression zone), select a moment arm, jd approximately equal to 0.95d.Assume that in.
in2
Recalculate ‘a’ for the actual As = 1.23 in.2: in.
in.
Therefore, the assumption that section is tension-controlled is valid.
in.2
Use 2-#7 bundled bars with in2 > in2 o.k.
Figure 2.2.3.1 – Cross-sectional view at joist mid-span (Section 2/2.2 in Figure 2.2)
Figure 2.2.3.2 – Cross-sectional view at joist near support face (Section 3/2.2 in Figure 2.2)
From Table 2.2.2.2 above, the shear value in end span at face of first interior support governs.
kips
The design shear at a distance, d, away from the face of support,
kips / ft
Shear strength provided by concrete
ACI 318-14 (Eq. 22.5.5.1)
lb kips
Since, shear reinforcement is required.
Try # 3, Grade 60 double-leg stirrups with a 90° hook.
The nominal shear strength required to be provided by shear reinforcement is
kips
Check whether Vs is less than
If Vs is greater than, then the cross-section has to be revised as ACI 318-14 limits the shear capacity to be provided by stirrups to. ACI 318-14 (22.5.1.2)
lb kips
Since does not exceed. The cross-section is adequate.
Assume # 3 stirrups with two legs ( in2)
Calculate the required stirrup spacing as
in.
Check whether the required spacing based on the shear demand meets the spacing limits for shear reinforcement per ACI 318-14 (9.7.6.2.2).
Check whether Vs is less than
lb kips > Vs = 12.6 kips
Therefore, maximum stirrup spacing shall be the smallest of d/2 and 24 in. ACI 318-14 (Table 9.7.6.2.2)
This value governs over the required stirrup spacing of 19.7 in which was based on the demand.
Joist minimum shear reinforcement requirements must be checked since wide-module joists do not satisfy ACI 318-14 (9.8).
Check the maximum stirrup spacing based on minimum shear reinforcement
in. (does not govern) ACI 318-14 (10.6.2.2(a))
in. (does not govern) ACI 318-14 (10.6.2.2(b))
Therefore, smax value is governed by the spacing limit per ACI 318-14 (9.7.6.2.2), and is equal to 9.35 in.
Use #3 @ 9 in. stirrups
ACI 318-14 (22.5.1.1 and 22.5.10.5.3)
kips
kips > kips o.k.
Compute where is equal to, and the stirrups can be stopped
At interior end of the exterior span, use 16-#3 @ 9 in o.c., Place 1st stirrup 2 in. from the face of supporting girder.
Since the preliminary joist depth met minimum depth requirement, the deflection calculations are not required. A lesser depth maybe possible and consequently cost savings can be achieved through deflection computations. Deflection values are calculated and provided for every model created by spBeam Program and can be used by the engineer to make additional optimization decisions.
spBeam Program can be utilized to analysis and design the one-way wide-module joist. A single wide-module joist is modeled as a five span continuous-beam.
The program calculates the internal forces (shear force and bending moment), moment and shear capacities, immediate and long-term deflection results, and required flexural reinforcement. The graphical and text results are provided here for both input and output of the spBeam model.
The ribs are modeled as a rectangular longitudinal beam with an equivalent width of 7.33 in. and 21 in. depth to reflect the sloped sides of the forming pans.
Figure 2.2.6.1 – spBeam Model –One-Way Joist Section
Figure 2.2.6.2 – spBeam Model – Isometric View – One-Way Joist
Figure 2.2.6.3 – spBeam Model – Loads (Including Live Load Patterning)
Figure 2.2.6.4 – spBeam Model – Internal Forces (Shear Force Diagram and Bending Moment Diagram)
Figure 2.2.6.5 – spBeam Model – Moment Capacity Diagram
Figure 2.2.6.6 – spBeam Model – Shear Capacity Diagram
Figure 2.2.6.7 – spBeam Model – Immediate Deflection Diagram
Figure 2.2.6.8 – spBeam Model – Reinforcement Diagram
Table 2.2.7.1 – Comparison of Hand Solution with spBeam Solution |
||||||
Flexural Design |
||||||
Span Location |
Design Moment (ft-kips) |
Reinforcement Required for Flexure (in2) |
Reinforcement Provided for Flexure (in2) |
|||
End Span |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Interior Negative |
136.6 |
128.46 |
1.78 |
1.658 |
6-#5 |
6-#5 |
Positive |
98.2 |
88.98 |
1.18 |
1.064 |
2-#7 |
2-#7 |
Shear Design |
||||||
Span Location |
Vu (kips) |
φVn (kips) |
||||
End Span |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
||
Interior Negative |
23.9 |
22.96 |
35 |
35.44 |
In this design example, the one-way joist system is modeled as a continuous T-beam representing single one-way joist. There is a good agreement between the hand solution and computer solution. Note that the coefficients traditionally used to determine moments do not address various types of support and geometry.
The maximum calculated total immediate (instantaneous) deflection (DL + LL) = 0.316 in., this value can be compared with maximum permissible calculated deflection limitation per project criteria in accordance to ACI 318-14. ACI 318-14 (Table 24.2.2)
In addition to deflection results, parametric studies can be performed in spBeam to optimize design and detailing results. With a minimum spacing of 1 in. between the 2-#7, two stirrups, and 1.5 in. cover on each side, a total width of 6.5 in. is required. The rib width at the bar level is 6.385 in. which is slightly less than required. For detailing purposes, one of the following options can be used:
1. Bottom bars can be bundled. This practice is often found in joist construction.
2. Stirrups can be rotated by a small angle to preserve the minimum spacing.
3. Bottom bars can be raised sufficiently to achieve the required width taking into the account the reduction into the moment capacity.
4. Other detailing options provided by the builder/formwork supply.
Figure 2.2.8 – Joist Cross-Section
In wide-module joist construction, the supporting beam, sometimes referred to as girder, depth is typically set to match the overall joist depth. Therefore, the beam depth is set to 21 in. This depth need to satisfy the minimum depth requirement of ACI 318-14 (Table 9.3.1.1) so that the deflection computations can be waived.
Using the minimum depth for non-prestressed beams in Table 9.3.1.1.
End Span: in (governs) < 21 in. ACI 318-14 (Table 9.3.1.1)
Interior Span: in ACI 318-14 (Table 9.3.1.1)
Therefore, the preliminary beam depth satisfies the minimum depth requirement.
Figure 2.3 – Partial plan view showing interior beam along grid B
Beam (girder) design involves the following steps:
2.3.1. Determination of span loads
2.3.2. Determination of design moments and shears
2.3.3. Flexural Design
2.3.4. Shear Design
2.3.5. Deflections
2.3.6. Computer Program Solution
2.3.7. Summary and comparison of design results
2.3.8. Conclusions and observations
Dead Load:
Try 36 in width for the beam (slightly larger than the column width that helps facilitate the forming, and reduces the beam longitudinal vs. column vertical bar interference)
Joist & Slab Weight kips/ft
Beam Weight kips/ft
Superimposed Dead Load, SDL kips/ft
Live Load:
Check for live load reduction per ASCE/SEI 7-10
ASCE/SEI 7-10 (Eq. 4-1)
Where:
reduced design live load per ft2 of area supported by the member
unreduced design live load per ft2 of area supported by the member = 80 psf
live load element factor = 2 for interior beams ASCE/SEI 7-10 (Table 4-2)
tributary area ft2
psf
Which satisfies requirement for members supporting one floor.
ASCE/SEI 7-10 (4.7.2)
kips/ft
Load Combination:
The following gravity load combinations are considered:
ACI 318-14 (Eq. 5.3.1a)
kips/ft
ACI 318-14 (Eq. 5.3.1b)
kips/ft
The span loads are governed by the second load combination.
The factored moment and shear can be determined using the simplified method if the requirements are satisfied: ACI 318-14 (6.5.1)
ü Members are prismatic.
ü Loads are uniformly distributed.
ü L ≤ 3D (1.52 kips/ft ≤ 3 x 3.83 kips/ft)
ü There are at least two spans.
ü The longer of two adjacent spans does not exceed the shorter by more than 20 percent.
Thus, the approximate coefficients can be used. The factored moment and shear are determined and summarized in the following tables. ACI 318-14 (Table 6.5.2 and Table 6.5.3)
Table 2.3.2.1 – Interior Beam Design Moment Values |
||
Location |
Design Moment Value |
|
End Spans |
Exterior Support Negative |
ft-kips |
Mid-span |
ft-kips |
|
Interior Support Negative |
ft-kips |
|
Interior Spans |
Mid-span Positive |
ft-kips |
Support Negative |
ft-kips |
Table 2.3.2.2 – Interior Beam Design Shear Values |
|
Location |
Design Shear Value |
End Span at Face of First Interior Support |
kips |
At Face of all other Supports |
kips |
For this interior beam, the end span moment values govern the design as tabulated in Table 2.3.2.1.
Calculate the required reinforcement to resist the first interior support negative moment:
ft-kips
Use #8 bars with 1.5 in. concrete cover per ACI 318-14 (Table 20.6.1.3.1). To avoid interference with joist negative moment reinforcement, the clear cover to the girder top reinforcement is required to be increased by lowering the girder top reinforcement. The distance from extreme compression fiber to the centroid of longitudinal tension reinforcement, d, is calculated below:
in.
To determine the area of steel, assumptions have to be made whether the section is tension or compression controlled, and regarding the distance between the resultant compression and tension forces along the slab section (jd). In this example, tension-controlled section will be assumed so the reduction factoris equal to 0.9, and jd will be taken equal to 0.9d since we are designing for the negative moment in a rectangular beam (narrow compression zone). The assumptions will be verified once the area of steel is finalized.
Assumein.
Interior beam width, in.
The required reinforcement at initial trial is calculated as follows:
in.2
Recalculate ‘a’ for the actual As = 7.59 in.2:
in.
Therefore, the assumption that section is tension-controlled is valid.
The minimum reinforcement shall not be less than
ACI 318-14 (9.6.1.2(a))
And not less than
ACI 318-14 (9.6.1.2(b))
Provide 10 - # 8 bars:
in2 in2 o.k.
Maximum spacing allowed:
Check the requirement for distribution of flexural reinforcement to control flexural cracking:
ACI 318-14 (Table 24.3.2)
in.
Use ksi ACI 318-14 (24.3.2.1)
in. (governs)
in.
Spacing provided for 10-# 8 bars in. in. o.k.
Where ds = 2.625 in. for #3 stirrup as shown in the following Figure. CRSI 2002 (Figure 12-9)
Figure 2.3.3 – Maximum number of bars in beams
Check the spacing, s provided, is greater than the minimum center to center spacing, smin where
CRSI 2002 (Figure 12-9)
Where maximum aggregate size is ¾”
Since the spacing provided is greater than 2 in. Therefore, 10-#8 bars are o.k.
All the values on Table 2.3.3.1 are calculated based on the procedure outlined above.
Table 2.3.3.1 – Reinforcing Design Summary |
|||||
|
End Span |
Interior Span |
|||
|
Exterior Negative |
Positive |
Interior Negative |
Positive |
Negative |
Design Moment, Mu (ft-kips) |
348.2 |
397.9 |
553.5 |
344 |
500.3 |
Effective depth, d (in.) |
18.0* |
18.625** |
18* |
18.625** |
18* |
As req’d (in.2) |
4.53 |
5.03 |
7.45 |
4.31 |
6.68 |
As min (in.2) |
2.29 |
2.37 |
2.29 |
2.37 |
2.29 |
Reinforcement |
6-#8 |
7-#8 |
10-#8 |
6-#8 |
9-#8 |
* The beam top bars are to be placed below the joist top bars. |
|||||
** The beam bottom bars are to be placed at the bottom-most layer. The joist bottom bars, then, shall be spliced at joist-beam intersection. |
From Table 2.3.2.2 above, the shear value in end span at face of first interior support governs.
kips
The design shear at a distance, d, away from the face of support,
kips
Shear strength provided by concrete
ACI 318-14 (Eq. 22.5.5.1)
lb kips
Since, shear reinforcement is required.
Try # 3, Grade 60 four-leg stirrups (Av = 0.44 in.2) with a 90° hook.
The nominal shear strength required to be provided by shear reinforcement is
kips
Check whether Vs is less than
If Vs is greater than, then the cross-section has to be revised as ACI 318-14 limits the shear capacity to be provided by stirrups to. ACI 318-14 (22.5.1.2)
lb kips
Since does not exceed. The cross-section is adequate.
Calculate the required stirrup spacing as
in. ACI 318-14 (22.5.10.5.3)
Check whether the required spacing based on the shear demand meets the spacing limits for shear reinforcement per ACI 318-14 (9.7.6.2.2).
Check whether Vs is less than
lb kips > Vs = 46 kips
Therefore, maximum stirrup spacing shall be the smallest of d/2 and 24 in. ACI 318-14 (Table 9.7.6.2.2)
This value governs over the required stirrup spacing of 19.7 in which was based on the demand. Note that since the stirrup spacing is governed by smax, the size of the stirrup can be kept as # 3. Selecting # 4 stirrup size will produce capacity more than what is required and therefore, be uneconomical.
Check the maximum stirrup spacing based on minimum shear reinforcement
in. (does not govern) ACI 318-14 (10.6.2.2(a))
in. (does not govern) ACI 318-14 (10.6.2.2(b))
Therefore, smax value is governed by the spacing limit per ACI 318-14 (9.7.6.2.2), and is equal to 9 in.
Use # 3 @ 8 in. stirrups
ACI 318-14 (22.5.1.1 and 22.5.10.5.3)
kips
kips > kips o.k.
Compute where is equal to, and the stirrups can be stopped
At interior end of the exterior span, use 16-# 3 @ 8 in o.c., Place 1st stirrup 2 in. from the face of the column.
Since the preliminary beam depth met minimum depth requirement, the deflection calculations are not required. A lesser depth maybe possible and consequently cost savings can be achieved through deflection computations. Deflection values are calculated and provided for every model created by spBeam Program and can be used by the engineer to make additional optimization decisions.
spBeam Program can be utilized to analyze and design the interior continuous beam along grid B. The beam is modeled as a three span continuous rectangular beam.
The program calculates the internal forces (shear force and bending moment), moment and shear capacities, immediate and long-term deflection results, and required flexural reinforcement. The graphical and text results are provided here for both input and output of the spBeam model.
The beam is modeled as a 36 in. by 21 in. deep rectangular longitudinal beam with column supports. The supports can be modeled as pinned, fixed, or using actual geometric properties of the beam-column joint. A value of 100 is used in this model for column stiffness share, indicating the actual column stiffness. When the percentage lies between zero and 100%, the joint stiffness contribution by the column is multiplied by that percentage. The default value is 100%.
Figure 2.3.6.1 – spBeam Model – Support Data
Figure 2.3.6.2 – spBeam Model – Isometric View – Interior Continuous Beam along Grid B
Figure 2.3.6.3 – spBeam Model – Loads (Including Live Load Patterning)
Figure 2.3.6.4 – spBeam Model – Internal Forces (Shear Force Diagram and Bending Moment Diagram)
Figure 2.3.6.5 – spBeam Model – Moment Capacity Diagram
Figure 2.3.6.6 – spBeam Model – Shear Capacity Diagram
Figure 2.3.6.7 – spBeam Model – Immediate Deflection Diagram
Figure 2.3.6.8 – spBeam Model – Reinforcement Diagram
Table 2.3.7.1 – Comparison of Hand Solution with spBeam Solution |
||||||
Flexural Design |
||||||
Span Location |
Design Moment (ft-kips) |
Reinforcement Required for Flexure (in2) |
Reinforcement Provided for Flexure (in2) |
|||
End Span |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Interior Negative |
553.5 |
486.01 |
7.51 |
6.45 |
10-#8 |
9-#8 |
Positive |
344 |
316.4 |
4.22 |
3.94 |
6-#8 |
5-#8 |
Shear Design |
||||||
Span Location |
Vu (kips) |
φVn (kips) |
||||
End Span |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
||
Interior Negative |
103.2 |
95.14 |
112.9 |
109.45 |
In this design example, the interior beam is modeled as a continuous rectangular longitudinal beam. There is a good agreement between the hand solution and computer solution. Note that the coefficients traditionally used to determine moments do not address various types of support and geometry.
The maximum calculated total immediate (instantaneous) deflection (DL + LL) = 0.529 in., this value can be compared with maximum permissible calculated deflection limitation per project criteria in accordance to ACI 318-14. ACI 318-14 (Table 24.2.2)
In addition to deflection results, parametric studies can be performed in spBeam to optimize design and detailing results.
The reinforcement diagram (Figure 2.3.6.8) shows the minimum length required (including the development length) for flexural design. The bars can be extended and detailed to provide the required support for shear stirrups.
Figure 2.3.8 – Interior Beam Cross-Section (Near the First Interior Support)
In the wide-module joist construction, the supporting beam depths shall be same as the overall joist depth. Therefore, the beam depth is set to 21 in. This beam depth need to satisfy the minimum depth requirement of ACI 318-14 (Table 9.3.1.1) so that the deflection computations can be waived. The beams of the exterior frame shall be designed and detailed for the combined effects of flexure, shear, and torsion according to ACI 318.
Using the minimum depth for non-prestressed beams in Table 9.3.1.1.
End Span: in (governs) < 21 in. ACI 318-14 (Table 9.3.1.1)
Interior Span: in ACI 318-14 (Table 9.3.1.1)
Therefore, the preliminary beam depth satisfies the minimum depth requirement.
Figure 2.4 – Partial plan view showing interior beam along grid B
Beam (girder) design involves the following steps:
2.4.1. Determination of span loads
2.4.2. Determination of design moment, shear, and torsion
2.4.3. Flexural and torsion design
2.4.4. Shear and torsion design
2.4.5. Deflections
2.4.6. Computer program solution
2.4.7. Summary and comparison of design results
2.4.8. Conclusions and observations
Dead Load:
Try 24 in width for the beam (slightly larger than the column width that helps facilitate the forming, and reduces the beam longitudinal vs. column vertical bar interference)
Joist & Slab Weight kips/ft
Beam Weightkips/ft
Superimposed Dead Load, SDL kips/ft
Live Load:
Check for live load reduction per ASCE/SEI 7-10
ASCE/SEI 7-10 (Eq. 4-1)
Where:
reduced design live load per ft2 of area supported by the member
unreduced design live load per ft2 of area supported by the member = 80 psf
2 (edge beams without cantilever slabs) ASCE/SEI 7-10 (Table 4-2)
tributary area ft2
psf
Which satisfies requirement for members supporting one floor. ASCE/SEI 7-10 (4.7.2)
kips/ft
Load Combination:
The following gravity load combinations are considered:
ACI 318-14 (Eq. 5.3.1a)
kips/ft
ACI 318-14 (Eq. 5.3.1b)
kips/ft
The span loads are governed by the second load combination.
For factored torsional moment calculations, the beam self-weight is not included since it is applied along the beam section centerline. And the moment arm is the distance from the midspan to the centerline of the exterior beam section = 16/2 – (24/2 - 20/2)/12 = 7.83 ft.
Thus, the following load combinations are used for the calculation of the factored torsional moment:
ACI 318-14 (Eq. 5.3.1a)
kips.ft/ft
ACI 318-14 (Eq. 5.3.1b)
kips.ft/ft
The span factored torsional moments are governed by the second load combination.
The factored moment and shear can be determined using the simplified method if the requirements are satisfied: ACI 318-14 (6.5.1)
ü Members are prismatic.
ü Loads are uniformly distributed.
ü L ≤ 3D (0.97 kips/ft ≤ 3 x 2.10 kips/ft)
ü There are at least two spans.
ü The longer of two adjacent spans does not exceed the shorter by more than 20 percent.
Thus, the approximate coefficients can be used. The factored moments and shears are determined and summarized in the following tables. ACI 318-14 (Table 6.5.2 and Table 6.5.3)
Table 2.4.2.1 – Exterior Beam Design Flexural Moment Values |
||
Location |
Design Flexural Moment Value |
|
End Spans |
Exterior Support Negative |
ft-kips |
Mid-span |
ft-kips |
|
Interior Support Negative |
ft-kips |
|
Interior Spans |
Mid-span Positive |
ft-kips |
Support Negative |
ft-kips |
Table 2.4.2.2 – Exterior Design Shear Values |
|
Location |
Design Shear Value |
End Span at Face of First Interior Support |
kips |
At Face of all other Supports |
kips |
Any structural analysis method can be used to calculate the torsional. The following table shows the torsional moment values at the centerline of the supports:
Table 2.4.2.3 – Exterior Design Torsional Moment Values |
|
Location |
Design Torsional Moment Value |
At the centerline of all Supports |
ft-kips |
For this exterior beam, the end span moment values govern the design as tabulated in Table 2.4.2.1.
Calculate the required reinforcement to resist the first interior support negative moment:
ft-kips
Use #8 bars with 1.5 in. concrete cover per ACI 318-14 (Table 20.6.1.3.1). To avoid interference with joist negative moment reinforcement, the clear cover to the girder top reinforcement is required to be increased by lowering the girder top reinforcement. The distance from extreme compression fiber to the centroid of longitudinal tension reinforcement, d, is calculated below:
To determine the area of steel, assumptions have to be made whether the section is tension or compression controlled, and regarding the distance between the resultant compression and tension forces along the slab section (jd). In this example, tension-controlled section will be assumed so the reduction factoris equal to 0.9, and jd will be taken equal to 0.9d since we are designing for the negative moment in a rectangular beam (narrow compression zone). The assumptions will be verified once the area of steel is finalized.
Assumein.
Interior beam width, in.
The required reinforcement at initial trial is calculated as follows:
in.2
Recalculate ‘a’ for the actual As = 4.49 in.2:
in.
Therefore, the assumption that section is tension-controlled is valid.
The minimum reinforcement shall not be less than
ACI 318-14 (9.6.1.2(a))
And not less than
ACI 318-14 (9.6.1.2(b))
All the values on the following table are calculated based on the procedure outlined above.
Table 2.4.3.1 – Reinforcing Design Summary (Flexure only) |
|||||
|
End Span |
Interior Span |
|||
|
Exterior Negative |
Positive |
Interior Negative |
Positive |
Negative |
Design Moment, Mu (ft-kips) |
204.7 |
233.9 |
327.5 |
204.7 |
297.7 |
Effective depth, d (in.) |
18.0* |
18.625** |
18.0* |
18.625** |
18.0* |
As, req’d (in.2) |
2.65 |
2.93 |
4.36 |
2.55 |
3.94 |
As, min (in.2) |
1.53 |
1.58 |
1.53 |
1.58 |
1.53 |
* The beam top bars are to be placed below the joist top bars. |
|||||
** The beam bottom bars are to be placed at the bottom-most layer. The joist bottom bars, then, shall be spliced at joist-beam intersection. |
Torsion requirements for longitudinal steel have to be determined and combined with reinforcement area required for flexure.
Calculate the required reinforcement to resist torsion:
Check if torsional effects can be neglected:
If Tu < φTth, it shall be permitted to neglect torsional effects. ACI 318-14 (22.7.1.1)
Where:
ft-kips
ft-kips = Threshold torsion (the calculation of φTth is shown in the next section)
Since Tu > φTth, the torsional effects must be considered.
Check if the factored design torsion can be reduced:
It is permitted to reduce Tu to φTcr; due to redistribution of internal forces after torsional cracking; if the exterior continuous beam meet the following requirements: ACI 318-14 (22.7.3.2)
1. The beam is statically indeterminate (continuous beam).
2. Tu ≥ φTcr.
To check the second condition, φTcr need to be calculated as follows:
Since the beams are cast monolithically with slab and joists, Acp (area enclosed by outside perimeter of concrete cross section) and pcp (outside perimeter of concrete cross section) for the beam can include a portion of the adjoining slab. The effective width, be, of the overhanging flange must conform to ACI 318-14 (8.4.1.8):
in. (governs)
in.
in.2
in.
in.3
The torsional properties of the beam ignoring the overhanging flange are the following:
in.2
in.
in.3 > 2796 in.3
Therefore, consider the rectangular section. ACI 318-14 (9.2.4.4(b))
ACI 318-14 (Table 22.7.5.1(a))
in.-lbs = 49.9 ft-kips
ft-kips
Checking the second condition of ACI 318-14 (22.7.3.2):
ft-kips > ft-kips
Thus, ACI 318-14 permits to reduce Tu to φTcr.
ft-kips ACI 318-14 (22.7.3.2)
It is assumed that the torsional loading on the beam is uniformly distributed along the span.
Determine the adequacy of cross-sectional dimensions for the torsion:
For solid sections, the limit on shear and torsion is given by:
ACI 318-14 (22.7.7.1)
Where:
Aoh = area enclosed by centerline of outermost closed transverse torsional reinforcement.
ph = perimeter of centerline of outermost closed transverse torsional reinforcement.
Using d = 18.0 in., the factored shear force at the critical section located at a distance d from the face of the support is:
kips.
Also, the nominal shear strength provided by the concrete is:
ACI 318-14 (Eq. 22.5.5.1)
Using a 1.5-in. clear cover to # 3 closed stirrups at bottom and 2.125 in clear cover to # 3 closed stirrups at top.
in2
in
psipsi
Therefore, the section is adequate.
Determine the transverse reinforcement required for torsion:
ACI 318-14 (Eq. 22.7.6.1a)
Where
in2 ACI 318-14 (22.7.6.1.1)
ACI 318-14 (22.7.6.1.2(a))
Therefore,
in2 / in per leg
Determine the transverse reinforcement required for shear:
From Table 2.3.2.2 above, the maximum shear value occurs at the face of the first interior support in the end span.
kips
The design shear at a distance, d, away from the face of support,
kips
Shear strength provided by concrete
ACI 318-14 (Eq. 22.5.5.1)
lb kips
Since, shear reinforcement is required.
The nominal shear strength required to be provided by shear reinforcement is
kips
Check whether Vs is less than
If Vs is greater than, then the cross-section has to be revised as ACI 318-14 limits the shear capacity to be provided by stirrups to. ACI 318-14 (22.5.1.2)
lb kips
Since Vs does not exceed. The cross-section is adequate.
Calculate the required transverse reinforcement for shear as
in.2/in. ACI 318-14 (22.5.10.5.3)
Calculate total required transverse reinforcement for combined shear and torsion:
Minimum transverse reinforcement for shear and torsion is calculated as follows:
ACI 318-14 (9.6.4.2)
in.2/in. < 0.0626 in.2/in.
Then, provide
Calculate the required spacing:
Maximum spacing of transverse torsion reinforcement:
ACI 318-14 (9.7.6.3.3)
Maximum spacing of transverse shear reinforcement:
Check whether the required spacing based on the shear demand meets the spacing limits for shear reinforcement per ACI 318-14 (9.7.6.2.2).
Check whether Vs is less than
lb kips > Vs = 19.43 kips
Therefore, maximum stirrup spacing shall be the smallest of d/2 and 24 in.
ACI 318-14 (Table 9.7.6.2.2)
(governs)
Using a bundle of 2-#3 closed stirrups with 2 legs (area per leg in2), the required spacing, s, at the critical section is:
in in
Provide a bundle of 2-#3 closed stirrups with 2 legs spaced at 7 in. on center. #3 bars are selected for consistency with the transverse reinforcement size used for the joist and interior beam. The stirrups are bundled at outer legs to maintain A0 value in calculation of At/s for torsion. The bundle of 2-#3 bars are defined as user-defined reinforcement of size #2 in spBeam Program.
The designer may choose to utilize #4 closed stirrups with 2 legs at 6 in. on center alternatively.
In view of the shear and torsion distribution along the span length, this same reinforcement and spacing can be provided throughout the span length.
Calculate the additional required longitudinal reinforcement for torsion:
ACI 318-14 (Eq. 22.7.6.1b)
Where
in.2 ACI 318-14 (22.7.6.1.1)
ACI 318-14 (22.7.6.1.2(a))
Therefore,
in.2
The minimum total area of longitudinal torsional reinforcement:
ACI 318-14 (9.6.4.3)
in.2
Since Al > Al,min, use Al = 1.68 in.2
The longitudinal reinforcement is to be distributed around the perimeter of the stirrups, with a maximum spacing of 12 in. There shall be at least one longitudinal bar in each corner of the stirrups.
ACI318-14 (9.7.5.1)
Longitudinal bars shall have a diameter at least 0.042 times the stirrup spacing, but not less than 3/8 in.
ACI318-14 (9.7.5.2)
To meet the maximum spacing requirement, a bar has to be provided between corner bars at all four sides. This configuration leads to eight-bars; three at top, three at bottom, and one at each side. Therefore, the reinforcement area per bar is As = 1.68/8 = 0.21 in.2
Then, use #5 bars for longitudinal bars which also meets minimum bar diameter requirement of 3/8 in. Al shall be provided in addition to the required flexural reinforcement at the negative moment regions (support-top) and positive moment region (mid-span-bottom). At mid-span-top region where flexural reinforcement is not required for flexure, 3-#5 bars shall be provided. Class B lap splice is to be provided.
Table 2.4.3.2 – Reinforcing Design Summary (Flexure + Torsion) |
|||||
|
End Span |
Interior Span |
|||
|
Top Reinforcing for Exterior Negative Moment |
Bottom Reinforcing for Positive Moment |
Top Reinforcing for Interior Negative Moment |
Bottom Reinforcing for Positive Moment |
Top Reinforcing for Interior Negative Moment |
Required Longitudinal Reinforcement (in.2) |
2.65 |
2.93 |
4.36 |
2.55 |
3.94 |
Required Torsional Longitudinal Reinforcement (in.2) |
0.63 |
0.63 |
0.63 |
0.63 |
0.63 |
Required Total Longitudinal Reinforcement (in.2) |
3.28 |
3.56 |
4.99 |
3.18 |
4.57 |
Reinforcement |
5-#8 |
5-#8 |
7–#8 |
4-#8 |
6-#8 |
Maximum spacing allowed:
Check the requirement for distribution of flexural reinforcement to control flexural cracking:
ACI 318-14 (Table 24.3.2)
in.
Use ksi ACI 318-14 (24.3.2.1)
in. (governs)
in.
Spacing provided for 4-# 8 bars in. in. o.k.
Where ds = 2.625 in. for #3 stirrup. CRSI 2002 (Figure 12-9)
Check the spacing, s provided, is greater than the minimum center to center spacing, smin where
CRSI 2002 (Figure 12-9)
Where maximum aggregate size is ¾”
Spacing provided for 7-# 8 bars in. in. o.k.
Therefore, the reinforcement selections in the previous table meet the spacing requirements.
Since the preliminary beam depth met minimum depth requirement, the deflection calculations are not required. A lesser depth maybe possible and consequently cost savings can be achieved through deflection computations. Deflection values are calculated and provided for every model created by spBeam Program and can be used by the engineer to make additional optimization decisions.
spBeam Program can be utilized to analyze and design the exterior continuous beam along grid A. The beam is modeled as a three span continuous rectangular beam.
The program calculates the internal forces (shear force and bending moment), moment and shear capacities, immediate and long-term deflection results, and required flexural reinforcement. The graphical and text results are provided here for both input and output of the spBeam model.
The beam is modeled as a 24 in. by 21 in. deep rectangular longitudinal beam with column supports at 100% stiffness share.
The reinforcement database is selected as User-defined in order to define a bundle of 2-#3 bars as #2 with cross-sectional area of 0.22 in2. (Different than #2 defined earlier for welded wire).
Torsion analysis was engaged using the torsion analysis and design check box located on the solve options tab in the input dialog box. The design for torsion is based on a thin-walled tube, space truss analogy. spBeam allows both equilibrium and compatibility torsion conditions. In the equilibrium mode, which is assumed by default, unreduced total value of the torsional design moment is used in the design. In the compatibility mode, factored torsional moments that exceed cracking moment Tcr are reduced to the value of Tcr. However, it is user’s responsibility to determine which mode is appropriate and the program does not perform any redistribution of internal forces if compatibility torsion is selected. In this model, the following solve options were used.
Figure 2.4.6.1 – spBeam Model – Isometric View – Exterior Continuous Beam along Grid A
Figure 2.4.6.2 – spBeam Model – Loads (Including Live Load Patterning)
Figure 2.4.6.3 – spBeam Model – Internal Forces (Shear Force, Torsion, and Bending Moment Diagrams)
Figure 2.4.6.4 – spBeam Model – Moment Capacity Diagram
Figure 2.4.6.5 – spBeam Model – Shear Capacity Diagram
Figure 2.4.6.6 – spBeam Model – Immediate Deflection Diagram
Figure 2.4.6.7 – spBeam Model – Reinforcement Diagram
Table 2.4.6.1 – Comparison of Hand Solution with spBeam Solution |
||||||
Span |
Mu (ft-kips) |
Tu (ft-kips) |
At/s (in2/in per leg) |
|||
End Span |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Interior Negative |
327.5 |
281.9 |
49.9 |
49.9 |
0.0223 |
0.0223 |
Span |
Av/s (in2/in) |
(Av+2At)/s (in2/in) |
Al (in2) |
|||
End Span |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Hand Solution |
spBeam Solution |
Interior Negative |
0.018 |
0.011 |
0.0626 |
0.0555 |
1.68 |
1.68 |
Table 2.4.6.2 – Comparison of Hand Solution with spBeam Solution (Reinforcement) |
||||
Span Location |
Required Reinforcement Area for Flexure + Torsion (in2) |
Reinforcement Provided for Flexure + Torsion |
||
End Span |
Hand Solution |
spSlab Solution |
Hand Solution |
spSlab Solution |
Interior Negative |
4.91 |
3.716+1.680*(3/8)=4.346 |
Top Bar: 7-#8 |
Top Bar: 5-#8 + 3-#8 = 8-#8 |
Positive |
3.53 |
2.203+1.680*(3/8)=2.833 |
Bottom Bar: 5-#8 |
Bottom Bar: 3-#8 + 3-#8 = 6-#8 |
In this design example, the exterior beam is modeled as a continuous rectangular longitudinal beam. There is a good agreement between the hand solution and computer solution. Note that the coefficients traditionally used to determine moments do not address various types of support and geometry.
The maximum calculated total immediate (instantaneous) deflection (DL + LL) = 0.369 in., this value can be compared with maximum permissible calculated deflection limitation per project criteria in accordance to ACI 318-14. ACI 318-14 (Table 24.2.2)
In addition to deflection results, parametric studies can be performed in spBeam to optimize design and detailing results.
The following observations can be made regarding the reinforcement diagram (Figure 2.4.6.7):
· The longitudinal reinforcement for the flexural design only and does not include (Al).
· Al is shown in the text output report (Design Results) because it has to be detailed and distributed to meet the torsional spacing requirements:
o At least one longitudinal bar must be present at each corner of the stirrups.
o And a bar has to be provided between corner bars at all four sides to meet the maximum spacing requirement (max 12 in.).
o This configuration leads to eight-bars in this example: three at top, three at bottom, and one at each side.
o Then, for the top bar for the interior negative section for the end span we need:
1) The longitudinal reinforcement for the flexural design 5-#8 is required for flexure.
2) The longitudinal reinforcement for the torsional design 3-#8 (3 top bars of the 8 bars distributed around the perimeter of the stirrups). See Table 2.4.6.2.
o Also, for the bottom bar for the positive section for the end span we need:
3) The longitudinal reinforcement for the flexural design 3-#8 is required for flexure.
4) The longitudinal reinforcement for the torsional design 3-#8 (3 bottom bars of the 8 bars distributed around the perimeter of the stirrups). See Table 2.4.6.2.
· Transverse reinforcement shown reflects the total size and quantity of stirrups to resist the combined effects of shear and torsion.
· Top bars minimum length required (including the development length) for flexural design is shown. The bars can be extended and detailed to provide the required support for shear stirrups.
Figure 2.4.7 – Exterior Beam Cross-Section
This section includes the design of interior, edge, and corner columns using spColumn software. The preliminary dimensions for these columns were calculated previously in section 1.2.
Interior Column:
Total Factored Load on 1st story interior column (@ 1st interior support) are reorganized based on the calculations on section 1.2 as follows:
PD = Total service dead load kips
PL = Total service live loadkips
Mu,x = unbalance flexural moment at the Interior support for the interior beam (see Figure 2.3.6.3)
= 595.20 - 545.96 = 49.24 ft-kips
Mu,y = unbalance flexural moment at the interior support for the joist (see Figure 2.2.6.3)
=154.53 – 141.78 = 12.75 ft-kips
The factored loads are then input into spColumn to construct the axial load – moment interaction diagram as shown in the sample input below.
Edge (Exterior) Column:
Total Factored Load on 1st story edge column (@ 1st interior support) are reorganized based on the calculations on section 1.2 as follows:
PD = Total service dead load kips
PL = Total service live load kips
Pu =
Mu,x = unbalance flexural moment at the Interior support (see Figure 2.4.6.3)
= 333.89 – 317.85 = 16.04 ft-kips
Mu,y = torsional moment at the Interior support for the exterior beam (see Section 2.4.3) + unbalance flexural moment at exterior support for the joist (see Figure 2.2.6.3)
= 2Tu + 73.96 = 2 x 49.9 + 73.96 = 173.76 ft-kips
Corner Column:
Total Factored Load on 1st story corner column (@ exterior support) are reorganized based on the calculations on section 1.2 as follows:
PD = Total service dead load kips
PL = Total service live load kips
Pu =
Mu,x = unbalance flexural moment at the Exterior support (see Figure 2.4.6.3) = 250.25 ft-kips
Mu,y = torsional moment at the Exterior support for the exterior beam (see Section 2.4.3) + unbalance flexural moment at exterior support for the joist (see Figure 2.2.6.3)
= Tu + 73.96 = 49.9 + 73.96 = 123.86 ft-kips
The axial force and moment interaction diagram is constructed using spColumn based on geometry and load input shown below:
Interior Column:
Figure 2.5.2.1 – spColumn Model – Biaxial Moment Interaction
Figure 2.5.2.2 – spColumn Model –Axial Moment Interaction
Figure 2.5.2.3 – spColumn Model – Nominal and Factored Failure Surfaces
Edge (Exterior) Column:
Figure 2.5.2.4 – spColumn Model –Axial Moment Interaction
Corner Column:
Figure 2.5.2.5 – spColumn Model –Axial Moment Interaction