Design Data

Code

Building Code Requirements for Structural Concrete (ACI 318-19) and Commentary (ACI 318R-19)

References

Design Guide on the ACI 318 Building Code Requirements for Structural Concrete, First Edition, 2020 Concrete Reinforcing Steel Institute (CRSI), Example 14.11

spColumn Engineering Software Program Manual v10.10, STRUCTUREPOINT, 2023

Interaction Diagram - Barbell Concrete Shear Wall Unsymmetrical Boundary Elements (ACI 318-19)” Design Example, STRUCTUREPOINT, 2022

Interaction Diagram - Building Elevator Reinforced Concrete Core Wall Design Strength (ACI 318-19)” Design Example, STRUCTUREPOINT, 2022

Biaxial Bending Interaction Diagrams for C-Shaped Concrete Core Wall Design (ACI 318-19)” Design Example, STRUCTUREPOINT, 2022

Interaction Diagram - Tied Reinforced Concrete Column with High-Strength Reinforcing Bars (ACI 318-19)” Design Example, STRUCTUREPOINT, 2022

Contact support@StructurePoint.org to obtain supplementary materials (spColumn models: CRSI-Ex-14-11.colx and CRSI-Ex-14-11-Mpr.colx)

Design Data

fc = 6,000 psi

fy = 80,000 psi

Clear cover = 0.75 in.

Story heights = 11 ft

Number of stories = 30

lw = 32.0 ft (Required extent of special boundary elements)

Table 1 - Wall Loads

Load Case

Axial Load,

kip

Bending Moment,

ft-kip

Shear Force,

kip

Dead, D

15,766.1

0

0

Live, L

4,594.4

0

0

Roof Live, Lr

47.1

---

---

Seismic, Qe

0

±163,801

±901.3

Table 2 - Wall Factored Loads

ACI Eq.

Reference

No.

Load Combination

Axial Load,

kip

Bending Moment,

ft-kip

Shear Force,

kip

5.3.1a

1

1.4D

22,072.5

0

0

5.3.1b

2

1.2D + 1.6L + 0.5Lr

26,293.9

0

0

5.3.1c

3

1.2D + 0.5L + 1.6Lr

21,291.9

0

0

5.3.1e

4

1.3D + 0.5L + 1.3Qe

SSR

22,793.1

-212,941.3

-1,171.7

5

SSL

22,793.1

-212,941.3

-1,171.7

5.3.1g

6

0.8D + 1.3Qe

SSR

12,612.9

-212,941.3

-1,171.7

7

SSL

12,612.9

-212,941.3

-1,171.7

SSR = sidesway to the right, SSL = sidesway to the left