2. Alternative Method for Out-of-Plane Slender Wall Analysis Applicability

Precast concrete walls can be analyzed using the provisions of Chapter 11 of the ACI 318-14. Most walls, and especially slender walls, are widely evaluated using the “Alternative Method for Out-of-Plane Slender Wall Analysis” in Section 11.8. The requirements of this procedure are summarized below:

The cross section shall be constant over the height of the wall

ACI 318-14 (11.8.1.1(a))

The wall can be designed as simply supported

ACI 318-14 (11.8.2.1)

Maximum moments and deflections occurring at midspan

ACI 318-14 (11.8.2.1)

The wall must be axially loaded

ACI 318-14 (11.8.2.1)

The wall must be subjected to an out-of-plane uniform lateral load

ACI 318-14 (11.8.2.1)

The wall shall be tension-controlled

ACI 318-14 (11.8.1.1(b))

The reinforcement shall provide design strength greater than cracking strength

ACI 318-14 (11.8.1.1(c))

Pu at the midheight section does not exceed 0.06 fc’Ag

ACI 318-14 (11.8.1.1(d))

Out-of-plane deflection due to service loads including effects does not exceed lc/150

ACI 318-14 (11.8.1.1(e))

ACI 318 requires that concentrated gravity loads applied to the wall above the design flexural section shall be assumed to be distributed over a width:

ACI 318-14 (11.8.2.2)

a) Equal to the bearing width, plus a width on each side that increases at a slope of 2 vertical to 1 horizontal down to the design section.

b) Not greater than the spacing of the concentrated loads.

c) Not extending beyond the edges of the wall panel.

ACI 318-14 (11.8.2.2)