9. Analysis and Design of the Section between the Design Strips

For the vertical reinforcement for the section between the design strips, minimum area of steel should be provided as follows:

ACI 318-14 (Table 11.6.1)

Try single layer panel reinforcement of 9 #4.

ACI 318-14 (2.2)

ACI 318-14 (11.7.2.1)